Extension Cords & Temporary Cords

Extension cords on jobsites get run over, pinched in doors, dragged over sharp edges and soaked in water. A damaged cord is one of the most common causes of jobsite shocks.

Photo: heavy-duty SJOOW cord with the jacket marking visible, next to a damaged cord

Use the right cord

Reading the jacket

The letters printed on the cord jacket tell you how tough it is:

LetterMeaning
SService cord, extra-hard usage (when it’s not followed by J)
JJunior service, hard usage, 300 volts
OOil-resistant outer jacket (OO means jacket and insulation are oil-resistant)
TThermoplastic (vinyl) jacket
EElastomer (rubber-like) jacket
WRated for wet and outdoor use, sunlight resistant

Example: SJOOW is a hard-service, oil-resistant, outdoor-rated cord. Light-duty household cords (like SPT “lamp cord”) don’t belong on a jobsite.

Size matters

A cord that’s too thin for the tool or too long overheats and starves the tool of voltage. Check the tool’s amp rating and the manual. A common guide for 120-volt tools:

Tool amps25 ft50 ft100 ft
Up to 10 A16 AWG16 AWG14 AWG
10 to 13 A16 AWG14 AWG12 AWG
13 to 15 A14 AWG12 AWG12 AWG or heavier

Lower numbers mean thicker wire. A cord that feels warm in use is a warning sign. Uncoil cords fully before running high loads, since coiled cords can overheat.

Inspect before each use

Remove damaged cords from service immediately. Cut the plug off or tag it if your company policy says so.

Protect cords on site

Assured grounding programs and color codes

Some construction employers use an assured equipment grounding conductor program instead of, or along with, GFCIs. Under that program, a competent person tests every cord, receptacle and cord-connected tool for ground continuity and correct wiring:

Many sites mark tested cords with a colored tape for each quarter. If your cord’s tape color is out of date, don’t use it. See GFCI Protection.

Storing cords