Electrical Test Meters

A meter is how you prove a circuit is dead before you touch it. The wrong meter, damaged leads, or a meter set to the wrong function can cause shocks, arc flashes, and false “dead” readings.

Photo: CAT III/CAT IV rated multimeter with shrouded test leads and a non-contact tester

Choose the right meter

Measurement categories

The CAT rating tells you how well a meter can survive a voltage spike (transient) without exploding in your hand. Spikes are bigger closer to the utility service.

CategoryWhere it appliesExamples
CAT IIPlug-in loads and receptacle circuitsAppliances, portable tools, wall outlets
CAT IIIBuilding distributionPanelboards, feeders, bus duct, motors, hard-wired equipment, lighting circuits
CAT IVOrigin of the installationService entrance, utility meter, overhead or underground service drop

A CAT IV 600 V meter is generally safer than a CAT III 1000 V meter at the service entrance. Look at both the category and the voltage.

Types of testers

Live-dead-live

  1. Test the meter on a known live source.
  2. Test the circuit you’re working on, phase to phase and phase to ground.
  3. Test the meter on the known live source again to prove it still works.

Safe use

Meter and lead check

Testing for absence of voltage is energized work. Until you prove the circuit is dead, treat it as live, and wear the shock and arc flash PPE the task requires. Only qualified workers should do it. See Qualified vs. Unqualified Workers and Lockout/Tagout.

Standards & references

  • NFPA 70E: Test instruments and equipment
  • 29 CFR 1910.334(c): Test instruments and equipment