NFPA 30: Flammable & Combustible Liquids

NFPA 30 is the code for storing and handling flammable and combustible liquids, from gasoline and solvents to diesel and lubricating oil. Fire codes and insurers rely on it, and OSHA has its own liquid rule (1910.106). This page explains the main ideas in plain language.

How liquids are classified

The classes depend on flash point: the lowest temperature at which a liquid gives off enough vapor to ignite. Vapors, not the liquid itself, burn.

GroupClassFlash pointExamples
FlammableIABelow 73°F, and boiling point below 100°FEthyl ether, some propellants
IBBelow 73°F, and boiling point at or above 100°FGasoline, many solvents
IC73°F or higher, and below 100°FTurpentine, some solvents and alcohols
CombustibleII100°F or higher, below 140°FDiesel, kerosene, some solvents
IIIA140°F or higher, below 200°FSome heavy oils
IIIB200°F or higherMany lubricating and hydraulic oils

Find the flash point and class on the container label and in Section 9 of the Safety Data Sheet. Hot liquids can act like a lower class when heated above their flash point. See Safety Data Sheets.

What NFPA 30 controls

Everyday safe handling

OSHA and NFPA 30

OSHA’s rule 1910.106 is based on earlier editions of NFPA 30 and sets the legal minimums for general industry. Construction has its own rules in 1926.152. NFPA 30 is updated more often and is usually more detailed, and fire marshals and insurers may require the current edition. Follow whichever is stricter, and ask your local authority.

Checklist for a liquid storage area

Note: This is a summary, and class limits, quantities and requirements are more detailed in the standard and local fire code. Use the edition your jurisdiction has adopted.

Standards & references

Last updated: